Introduction

Seawater leak detection is one of the post-condensation water quality management processes that are performed for power station boilers and similar facilities. Damage to the ion exchange resin, which deionizes the supplied water, is also monitored during this process, and both of these applications are executed by a conductivity analyzer.

Expected Benefits

  • Detects seawater leakage and ion exchange resin damage
  • Reduces operating cost

Process Overview

Boiler Water Quality Management Process

Boiler Water Quality Management Process

The above illustration shows where analyzers are used in the boiler water quality management process.

In the measurement point iab-app-x-en.gif shown in the figure, two different signal ranges are needed for deionized water management and seawater leak detection. The FLXA402 can simultaneously generate output signals for two different ranges, meaning that a single unit can perform deionized water management concurrently with seawater leak detection.

Other applications for this conductivity analyzer include the management of deionized boiler water.

Solution Details

Boiler Leak Detection

Measurement system 4-wire conductivity system
Converter FLXA402-A-B-☐-C1-NN-A2-WR-☐-☐-☐-NN
Sensor SC4A(J)-S-AD-09-002-☐☐-T1/PS
General Specifications
FLXA402 4-wire Conductivity Converter
Measuring range (at process temperature; C: cell constant)
[Conductivity] Minimum: 0 µ/cm
Maximum: 200 mS/cm x C (overrange: 2000 mS/cm)
[Resistivity] Minimum: 0.005 kΩ/C
Maximum: 1000 MΩ·cm
[Temperature] Pt1000: -20 to +250°C
Output setting range
[Conductivity] Minimum: 0.010 µS/cm
Maximum: 2000 mS/cm
[Resistivity] Minimum: 0.001 kΩ·cm
Maximum: 1000 MΩ·cm
[Temperature] Min. span: 25°C; Max. span: 270°C
Output signal: two or four outputs of 4-20 mA DC + HART
Construction: for outdoor installation, IP66, NEMA Type4X waterproof
Ambient operating temperature: -20 to +55°C
Power supply voltage: 90 to 264 V AC, 50/60 Hz
Power consumption: 35 VA maximum
SC4A(J) Conductivity Sensor
Electrode system: two-electrode system
Cell constant: 0.02 cm-1
Measuring range: 0 – 0.5 µS/cm to 0 – 200 µS/cm
Temperature range: 0 - 110°C
Wetted material: SUS316L, PEEK (polyether ether ketone) /PS Adapter (option code of SC4A(J))
Material: SUS316L
Operating pressure: 1 MPa maximum (depends on the SC4A(J) Sensor)

Industries

  • Cogeneration

    Cogeneration or combined heat and power (CHP) is an efficient approach to generating power and thermal energy from a single fuel source.

    See More
  • Combined Cycle

    The combined cycle power plant is being installed in increasing numbers around the world where there are substantial supplies of natural gas.

    See More
  • Power

    In the mid 1970s, Yokogawa entered the power business with the release of the EBS Electric Control System. Since then, Yokogawa has steadfastly continued with the development of our technologies and capabilities for providing the best services and solutions to our customers worldwide.

    Yokogawa has operated the global power solutions network to play a more active role in the dynamic global power market. This has allowed closer teamwork within Yokogawa, bringing together our global resources and industry know-how. Yokogawa's power industry experts work together to bring each customer the solution that best suits their sophisticated requirements.

    See More
  • Thermal

    Thermal power using coal, oil or gas as fuel accounts for the majority of electric generation throughout the world.

    See More

Related Products & Solutions

  • 2-Wire Transmitter/Analyzer FLXA202

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    See More
  • 2-Wire Transmitter/Analyzer FLXA21

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    See More
  • Contacting Conductivity Sensors SC42/SC4A(J)

    The measurement of specific conductivity in aqueous solutions is becoming increasingly important for the determination of impurities in water.  Yokogawa has designed a full range of precision sensors and instruments to cope with these measurements, even under extreme conditions.

    See More
  • Digital SMART SENCOM™ Adapter, SA11

    Reusable SMART adapter, requiring only the analog sensor to be disposed of when it reaches the end of its lifetime. With the SENCOM 4.0 platform, Yokogawa delivers reduced costs and waste while contributing to its long-term business goals of a sustainable future for all.

    See More

Top
宁晋县服装鞋帽有限公司兴隆台区机械配件有限公司霞山区管道配件有限公司松潘县电脑图文设计制作有限公司英山县酒店用品有限公司 成县销售有限公司团风县影视策划有限公司田林县产品包装开发有限公司正定县纺织助剂有限公司宜川县物业管理有限公司